Title: | Avaliação das taxas de infiltração de ar no sector residencial - estudo experimental de campo pelo método do CO2 metabólico | Authors: | Gomes, Maria de Fátima Teixeira Rocheta | Orientador: | Simões, Nuno Albino Vieira Silva, Manuel Carlos Gameiro da |
Keywords: | Infiltrações de ar; taxas de renovação horária; método dos gases traçadores; CO2 metabólico; edifícios residenciais; Air infiltration; air exchange rate; tracer gas method; metabolic CO2; residential buildings | Issue Date: | 24-Sep-2013 | metadata.degois.publication.location: | Coimbra | Abstract: | O consumo de energia final no sector residencial em Portugal tem aumentado desde há duas
décadas, contra a tendência da maioria dos países da União Europeia. A actual legislação
portuguesa sobre o desempenho térmico dos edifícios (RCCTE) também considera os
aspectos da Qualidade do Ar Interior (QAI). A taxa mínima regulamentar é de 0,6 renovações
horárias mas persiste a incerteza da sua magnitude nos edifícios novos e existentes. Devido
aos esforços para melhorar o isolamento da envolvente exterior dos edifícios residenciais, a
renovação do ar interior tornou-se um mecanismo relevante de dissipação de energia.
Pretende-se a avaliação das taxas de infiltração de ar no sector residencial, em condições de
ventilação natural, para uma melhor caracterização do parque habitacional e para a delineação
de estratégias de melhoria do desempenho energético dos edifícios e de poupança de energia.
Realizaram-se várias medições de campo em 20 residências do Distrito do Porto, em
condições de ocupação regular, utilizando as técnicas transientes do método dos gases
traçadores e o CO2 metabólico dos residentes como gás traçador.
As taxas de infiltração de ar obtidas variaram entre 0,15h-1 e 0,46h-1. Para a amostra estudada,
as taxas regulamentares actuais de renovação do ar variam entre 0,87h-1 e 1,2h-1, e entre 0,3h-1
e 2,65h-1 no futuro regulamento. Neste último, algumas das habitações de uma só fachada não
cumprem a nova taxa mínima regulamentar (0,4h-1) por inibirem a ventilação cruzada. As
restantes não cumprem a taxa de referência do novo regulamento (0,6h-1) por se considerarem
muito permeáveis ao ar mas verifica-se uma sobrestimação da pressão dinâmica do vento nas
fachadas. Não se obteve qualquer correlação com a extensão linear das caixilharias,
possivelmente devido à sua fraca permeabilidade ao ar. Excepto em três habitações, as
concentrações máxima absolutas de CO2 interiores são inferiores a 1500ppmv apesar de mais
de metade das habitações não cumprir os caudais de referência de ar novo por ocupante
(30m3.h-1 para salas de estar e quartos de edifícios residenciais, definidos no Regulamento dos
Sistemas Energéticos de Climatização em Edifícios-RSECE). Considera-se haver condições
ideais para a promoção e implementação de soluções inovadoras de ventilação natural
controlada baseadas em critérios exigenciais definidos pelos ocupantes residenciais, embora também seja necessária uma pesquisa sobre a QAI percepcionada através de métodos
indirectos. Final energy use in households in Portugal has been increasing for the last two decades, against the tendency in most EU countries. The current Portuguese regulation on the thermal performance of buildings (RCCTE) also considers Indoor Air Quality aspects (IAQ). The regulatory minimum infiltration rate is 0,6 air exchanges per hour but some uncertainty persists about its magnitude in the existing and newly built houses. Due to the efforts carried out to better insulate the envelopes of buildings, the indoor air renovation became a relevant mechanism of energy dissipation. The aim of this study is the assessment of air infiltration rates in the naturally ventilated residential buildings in order to design the strategies to improve energy performance and promote energy savings. Several series of trials were performed to measure the infiltration rate at 20 dwellings in the Oporto District, under regular occupation, using the tracer gas method by the metabolic CO2 of the residents as tracer gas. The obtained air infiltration rates varied between 0,15h-1 and 0,46h-1. For the studied sample, the regulatory air change rates rates vary between 0,87h-1 and 1,2h-1 and between 0,3h-1 and 2,65h-1 in the current and the future regulation, respectively. In the last one, some dwellings with a single facade do not meet the new minimum regulatory rate (0,4h-1) because they inhibit the cross ventilation. The others do not meet the reference air change rate of the future regulation (0,6h-1) because they are considered little airtight but there is an overestimation of the wind dynamic pressure on the facades. There is no correlation between the obtained infiltration rates and the window frame length factor, possibly due to its good air tightness. Except in three dwellings, the maximum indoor CO2 concentrations were lower than 1500ppmv, although more than half of the dwellings do not reach the reference fresh air flow rate per occupant (30m3.h-1 for living rooms and bedrooms in residential buildings, defined in the Regulation of Energy Systems for Climate Control in Buildings - RSECE). There are ideal conditions for the promotion and implementation of innovative solutions about demand controlled natural ventilation applied to the residential buildings, set up by their occupant’s requirements, although also a post-occupancy survey on the perceived IAQ through indirect methods is required. |
Description: | Dissertação de Mestrado em Energia para a Sustentabilidade apresentada à Faculdade de Ciências e Tecnologia da Universidade de Coimbra | URI: | https://hdl.handle.net/10316/38897 | Rights: | openAccess |
Appears in Collections: | UC - Dissertações de Mestrado FCTUC Eng.Mecânica - Teses de Mestrado |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
Dissertação_EFS_2009103309.pdf | 1.29 MB | Adobe PDF | View/Open |
Page view(s) 50
560
checked on Nov 6, 2024
Download(s)
227
checked on Nov 6, 2024
Google ScholarTM
Check
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.